FAQ: Why it shows alarm OC0 or OV0 on new installed AC drive with on load?

Shihlin Electric FAQ: Selection, Wiring & Troubleshooting

Why it shows alarm OC0 or OV0 on new installed AC drive with on load?

If the AC drive is placed under big power AC drive (beyond 1000kVA) or there's phase-advancing capacitor switch, power input circuit will have a high peak current, occurring alarm OC0 or OV0. Install an AC reactor in front of AC drive is suggested.