What should we do when error OV2 occurs?
OV2: Overvoltage occurs when the invereter operates at constant speed
1. Use a multimeter to detect whether the input power supply voltage is abnormal.
2. Check if the motor is grounded and try to change the grounding status (remove the ground wire if it is grounded in present; If it is not grounded in present, try to ground the motor)
3. If the inverter power supply is connected to other high-power equipment (such as large-capacity fans), its start and stop may affect the power quality, may also lead to the inverter to trigger OV2 alarm In this case, a AC input reactor should consider to be installed.