What should we do when error OPT occurs?
1. Check whether the communication cable connection is abnormal or disconnected
2. Check whether the communication protocol parameters of the upper controller (PC or PLC or other equipment) match with the parameters set by the inverter.
3. Check whether the alarm is caused by interference. ( The communication is normal or not when the inverter isn't operating or not connected to the motor.)
4. If it is confirmed to be caused by interference, please improve the wiring. Apply shielded wire and connect the shielding layer to the system communication ground at both ends.