What should we do when error ERR occurs?
There are a variety of conditions that may cause ERR, please confirm one by one according to the following instructions:
1. Insufficient power supply voltage, please use a multimeter to confirm whether the R-S-T AC voltage is in accordance with the user manual declaration and whether the P-N DC voltage is normal (not less than 240Vdc for 200V series and not less than 456Vdc for 400V series).
2. Whether the keypad connection cable is loose or whether the keypad and inverter are mismatched.
3. Whether the RES terminal on the control board is wired and in ON state.