FAQ: What should we do when error PG1 occurs?

Shihlin Electric FAQ: Selection, Wiring & Troubleshooting

What should we do when error PG1 occurs?

PG1: Encoder input error
The main cause of this error is wrong encoder input type setting
Please check the P.351 setting, which should normally be set to 1 or 2.Please refer to the user manual "PG feedback parameter group" section and PG card installation manual.